Items |
A-9597 Power Line HEMP Filters Legacy |
A-9598 Power Line HEMP Filters Legacy |
A-9599 Power Line HEMP Filters Legacy |
A-9600 Power Line HEMP Filters Legacy |
A-8292 Power Line HEMP Filters Legacy |
|||||
Voltage | N/A 0 to 480 V | |||||||||
Operating Temperature | N/A -40 to +71 ºC | |||||||||
Storage Temperature | N/A -55 to +105 ºC | |||||||||
Maximum Altitude | N/A 15000 ft | |||||||||
Humidity | N/A 10 to 90 % | |||||||||
Fungus | N/A Non-nutritive materials are used | |||||||||
Corrosion | N/A Hermetically sealed steel or aluminum enclosures with tin-lead plating | |||||||||
Maximum Dimension A | N/A 8.90 in | N/A 7.40 in | N/A 7.90 in | N/A 8.40 in | N/A | |||||
Dimension B | N/A 6.50 in | N/A 5.00 in | N/A 5.50 in | N/A 6.00 in | N/A | |||||
Note |
N/A
With HEMP protection devices removed. Full load from 100 KHz to 20 MHz. |
N/A
With HEMP protection devices removed. Full load from 100 KHz to 20 MHz. |
N/A
With HEMP protection devices removed. 600 Ω line to line and 300 Ω line to ground. Full load from 100 KHz to 20 MHz. |
N/A
With HEMP protection devices removed. 100 Ω line to line and 50 Ω line to ground. Full load from 100 KHz to 20 MHz. |
N/A
Full load from 100 KHz to 20 MHz. When tested with external V130LA20B MOV connected from each line to ground. |
|||||
Voltage (Vrms) | N/A 35 | N/A 132 | N/A 132 | N/A 35 | N/A 125 | |||||
Voltage (Peak) | N/A 50 | N/A 187 | N/A 187 | N/A 50 | N/A 177 | |||||
Current | N/A 2 A | N/A 2 A | N/A 1/2 A | N/A 1/2 A | N/A 5 A | |||||
Frequency | N/A DC-60 Hertz | N/A DC-60 Hertz | N/A DC-60 Hertz | N/A DC-60 Hertz | N/A DC to 60 Hertz | |||||
DCR | N/A ≤ 0.3 Ω | N/A ≤ 1.0 Ω | N/A ≤ 6.1 Ω | N/A ≤ 1.5 Ω | N/A ≤ 0.5 Ω | |||||
DWV (DC) | N/A 200 V | N/A 600 V | N/A 600 V | N/A 200 V | N/A 600 V | |||||
Passband Response (Limit) | N/A | N/A | N/A 0 to 3000 Hertz, 1 dB 0 to 3500 Hertz, 3 dB | N/A 0 to 3000 Hertz, 1 dB 0 to 3500 Hertz, 3 dB | N/A | |||||
MIL-STD-220 Insertion Loss (Limit) | N/A 100 dB Minimum from 14 kHz through 10 GHz | |||||||||
Type | N/A Short Pulse | |||||||||
Type of Injection | N/A Common Mode Wire-to-ground | |||||||||
Common Mode Peak Short- Circuit Current | N/A 5000 A | N/A 5000 A | N/A 5000 A | N/A 5000 A | N/A 2500 A | |||||
Wire-to-ground Peak Short- Circuit Current | N/A 2500 A | N/A 3536 A | N/A 3536 A | N/A 2500 A | N/A 2500 A | |||||
Common Mode Source Impedance | N/A ≥ 60 Ω | |||||||||
Wire-to-ground Source Impedance | N/A ≥ 60 Ω | |||||||||
Wire-to-ground Load Impedance | N/A 2 Ω | N/A 2 Ω | N/A 50 Ω | N/A 50 Ω | N/A 2 Ω | |||||
Common Mode Residual Peak Current | N/A ≤ 0.1 A | N/A ≤ 1.0 A | N/A ≤ 1.0 A | N/A ≤ 0.1 A | N/A ≤ 1.0 A | |||||
Wire-to-ground Residual Peak Current | N/A ≤ 0.1 A | N/A ≤ 1.0 A | N/A ≤ 1.0 A | N/A ≤ 0.1 A | N/A ≤ 1.0 A | |||||
Attributes/Options |
N/A
|
|||||||||
|