Print Back
  • Voltage Rating : 48 VDC or 120 VAC @ 0-60 Hz
  • Visual/Mechanical : Per MIL-PRF-15733, paragraph 4.6.1
  • Capacitance : Per MIL-STD-202, Method 305 @ 1 kHz
  • Insulation Resistance : Per MIL-PRF-15733, paragraph 4.6.7 with Hemp Protection Module removed.
  • Dielectric Withstanding Voltage : Per MIL-PRF-15733, paragraph 4.6.5 with Hemp Protection Module removed.
  • Standard Insertion Loss : Per MIL-STD-220, 20 dB @ 10 kHz, 80 dB @ 10 MHz to 10 GHz
  • Terminal Strength : Per MIL-PRF-15733, paragraph 4.6.11
  • Voltage Discharge : Discharge to less than 30 Volts within 2 seconds after removal of power
  • Terminals : 1/4" Quick Connect Tab
  • Operating Temperature : -55 ºC to +71 ºC
  • Storage Temperature : -55 ºC to +105 ºC
  • Chassis & Terminal Finish : Electro Tin-Lead
  • Chassis Material : 20 GA. Cold Rolled Steel
Control/Signal Line HEMP Filters Standard/High Performance
Control/Signal Line HEMP Filters Standard/High Performance - 2
Unit of Measure
1 

Item #

Item Name

Major Dimension A

Major Dimension B

Major Dimension C

Major Dimension D

CAD

A-10356 N/A 1/2 Ampere (A) Current Control/Signal Line HEMP Filter Standard Performance N/A 6.90 in N/A 4.50 in N/A 1.25 in N/A 2.50 in N/A CAD Icon
A-10357 N/A 2 Ampere (A) Current Control/Signal Line HEMP Filter Standard Performance N/A 6.90 in N/A 4.50 in N/A 1.50 in N/A 2.50 in N/A CAD Icon
A-10358 N/A 5 Ampere (A) Current Control/Signal Line HEMP Filter Standard Performance N/A 8.40 in N/A 6.00 in N/A 2.00 in N/A 3.00 in N/A CAD Icon
A-10360 N/A 1/2 Ampere (A) Current Control/Signal Line HEMP Filter Standard Performance N/A 6.40 in N/A 4.00 in N/A 1.25 in N/A 2.50 in N/A CAD Icon
A-10361 N/A 2 Ampere (A) Current Control/Signal Line HEMP Filter Standard Performance N/A 6.40 in N/A 4.00 in N/A 1.25 in N/A 2.50 in N/A CAD Icon
A-10362 N/A 5 Ampere (A) Current Control/Signal Line HEMP Filter Standard Performance N/A 10.40 in N/A 8.00 in N/A 1.50 in N/A 2.50 in N/A CAD Icon
Unit of Measure
1