CAD (0)
▾
- Voltage Rating : 48 VDC or 120 VAC @ 0-60 Hz
- Visual/Mechanical : Per MIL-PRF-15733, paragraph 4.6.1
- Capacitance : Per MIL-STD-202, Method 305 @ 1 kHz
- Insulation Resistance : Per MIL-PRF-15733, paragraph 4.6.7 with Hemp Protection Module removed.
- Dielectric Withstanding Voltage : Per MIL-PRF-15733, paragraph 4.6.5 with Hemp Protection Module removed.
- Standard Insertion Loss : Per MIL-STD-220, 20 dB @ 10 kHz, 80 dB @ 10 MHz to 10 GHz
- Terminal Strength : Per MIL-PRF-15733, paragraph 4.6.11
- Voltage Discharge : Discharge to less than 30 Volts within 2 seconds after removal of power
- Terminals : 1/4" Quick Connect Tab
- Operating Temperature : -55 ºC to +71 ºC
- Storage Temperature : -55 ºC to +105 ºC
- Chassis & Terminal Finish : Electro Tin-Lead
- Chassis Material : 20 GA. Cold Rolled Steel
Unit of Measure
Specifications
Major Dimensions
Major Dimension A |
N/A 6.40 in |
Major Dimension B |
N/A 4.00 in |
Major Dimension C |
N/A 1.25 in |
Major Dimension D |
N/A 2.50 in |
Chassis Material
Chassis Material |
N/A Cold Rolled Steel (CRS) |
Chassis Material Thickness |
N/A 20 gauge |