- Voltage Rating: 277/480 VAC @ 60 Hz
- Current Rating: 5 through 150 amperes
- HEMP Compliance: Per MIL-STD-188-125-1 and MIL-STD-188-125-2 as Power Line (Intrasite) point of entry filter for short (E1) and intermediate (E2) pulses.
- Insertion Loss: high performance (curve 2) per more
- Voltage Rating: 277/480 VAC @ 60 Hz
- Current Rating: 5 through 150 amperes
- HEMP Compliance: Per MIL-STD-188-125-1 and MIL-STD-188-125-2 as Power Line (Intrasite) point of entry filter for short (E1) and intermediate (E2) pulses.
- Insertion Loss: high performance (curve 2) per MIL-STD-220
- Leakage Current: < 10% of rated current 10 through 150 amperes, <1 amp for 5 amp filters
- Insulation Resistance: Per MIL-PRF-15733, prior to discharge resistor installation.
- Dielectric Withstanding Voltage: 2250 VDC line-to-chassis per MIL-STD-202, Method 301 prior to surge arrestor and discharge resistor installation
- Voltage Drop: Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733
- Voltage Discharge: Discharge to less than 30 Volts within 30 s after removal of power
- Operating Temperature: -40 ºC to +65 ºC
- Storage Temperature: -55 ºC to +105 ºC
Unit of Measure
Specifications
Brands |
N/A Captor |
Voltage Rating (AC) |
N/A 277 V480 V |
Frequency |
N/A 60 Hz |
Current |
N/A 150 A |
Insertion Loss Curve |
N/A
![]() Loading zoom Curve 2, High Performance Minimum Insertion Loss |
Number of Circuits |
N/A 4 |
Estimated Weight |
N/A 450 lb |
High Altitude Electromagnetic Pulse (HEMP) Compliance |
N/A Per MIL-STD-188-125-1 and MIL-STD-188-125-2 as Power Line (Intrasite) Point of Entry Filter for Short (E1) and Intermediate (E2) Pulses. |
Minimum Insertion Loss |
N/A 100 dB @ 14 kHz to 10 GHz |
Leakage Current |
N/A < 10% of Rated Current 10 through 150 Amperes, < 1 Amp for 5 Amp Filters |
Insulation Resistance |
N/A Per MIL-PRF-15733, prior to discharge resistor installation. |
Dielectric Withstanding Voltage |
N/A 2250 VDC Line-to-Chassis Per MIL-STD-202, Method 301 Prior to Surge Arrestor and Discharge Resistor Installation |
Voltage Drop |
N/A Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733 |
Voltage Discharge |
N/A Discharge to Less than 30 Volts within 30 s After Removal of Power |
Operating Temperature |
N/A -40 to +65 °C |
Storage Temperature |
N/A -55 to +105 °C |
Compliance |
N/A MIL-STD-188-125-1 MIL-STD-188-125-2 |
Dimensions
Dimension A |
N/A 28.0 in |
Dimension B |
N/A 50.0 in |
Dimension C |
N/A 12.0 in |
Dimension D |
N/A 44.0 in |
Dimension E |
N/A 30.0 in |
Enclosure
Enclosure |
N/A
|