Print Back
  • Voltage Rating: 277/480 VAC @ 60 Hz
  • Current Rating: 5 through 150 amperes
  • HEMP Compliance: Per MIL-STD-188-125-1 and MIL-STD-188-125-2 as Power Line (Intrasite) point of entry filter for short (E1) and intermediate (E2) pulses.
  • Insertion Loss: Standard performance (curve 1) per MIL-STD-220
  • Leakage Current: < 10% of rated current 10 through 150 amperes, < 1 amp for 5 amp filters
  • Insulation Resistance: Per MIL-PRF-15733, prior to discharge resistor installation.
  • Dielectric Withstanding Voltage: 2250 VDC line-to-chassis per MIL-STD-202, Method 301 prior to surge arrestor and discharge resistor installation
  • Voltage Drop: Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733
  • Voltage Discharge: Discharge to less than 30 Volts within 30 s after removal of power
  • Operating Temperature: -40 ºC to +65 ºC
  • Storage Temperature: -55 ºC to +105 ºC
Dimensional Drawing for Power Line HEMP Filters Standard Performance
Unit of Measure
Items Image
A-10540
5 Ampere (A) Current Power Line Stand Alone HEMP Filter Standard Performance
Image
A-10541
5 Ampere (A) Current Power Line Stand Alone HEMP Filter Standard Performance
Image
A-10542
5 Ampere (A) Current Power Line Stand Alone HEMP Filter Standard Performance
Image
A-10543
10 Ampere (A) Current Power Line Stand Alone HEMP Filter Standard Performance
Image
A-10544
10 Ampere (A) Current Power Line Stand Alone HEMP Filter Standard Performance
Description N/A
  • Voltage Rating: 277/480 VAC @ 60 Hz
  • Current Rating: 5 through 150 amperes
  • HEMP Compliance: Per MIL-STD-188-125-1 and MIL-STD-188-125-2 as Power Line (Intrasite) point of entry filter for short (E1) and intermediate (E2) pulses.
  • Insertion Loss: Standard performance (curve 1) per MIL-STD-220
  • Leakage Current: < 10% of rated current 10 through 150 amperes, < 1 amp for 5 amp filters
  • Insulation Resistance: Per MIL-PRF-15733, prior to discharge resistor installation.
  • Dielectric Withstanding Voltage: 2250 VDC line-to-chassis per MIL-STD-202, Method 301 prior to surge arrestor and discharge resistor installation
  • Voltage Drop: Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733
  • Voltage Discharge: Discharge to less than 30 Volts within 30 s after removal of power
  • Operating Temperature: -40 ºC to +65 ºC
  • Storage Temperature: -55 ºC to +105 ºC
Brands N/A Captor
Voltage Rating (AC) N/A 277 V480 V
Frequency N/A 60 Hz
Current N/A 5 A N/A 5 A N/A 5 A N/A 10 A N/A 10 A
Insertion Loss Curve N/A
Curve 1, Standard Performance Minimum Insertion Loss
Number of Circuits N/A 2 N/A 3 N/A 4 N/A 2 N/A 3
Dimension A N/A 9.00 in N/A 13.5 in N/A 18.00 in N/A 9.00 in N/A 13.5 in
Dimension B N/A 30.0 in
Dimension C N/A 5.5 in
Dimension D N/A 29.0 in
Dimension E N/A 8.0 in N/A 12.5 in N/A 17.0 in N/A 8.0 in N/A 12.5 in
Estimated Weight N/A 50 lb N/A 75 lb N/A 105 lb N/A 60 lb N/A 90 lb
High Altitude Electromagnetic Pulse (HEMP) Compliance N/A Per MIL-STD-188-125-1 and MIL-STD-188-125-2 as Power Line (Intrasite) Point of Entry Filter for Short (E1) and Intermediate (E2) Pulses.
Minimum Insertion Loss N/A 20 dB @ 10 kHz 40 dB @ 100 kHz 60 dB @ 1 MHz 80 dB @ 10 MHz to 10 GHz
Leakage Current N/A < 10% of Rated Current 10 through 150 Amperes, < 1 Amp for 5 Amp Filters
Insulation Resistance N/A Per MIL-PRF-15733, prior to discharge resistor installation.
Dielectric Withstanding Voltage N/A 2250 VDC Line-to-Chassis Per MIL-STD-202, Method 301 Prior to Surge Arrestor and Discharge Resistor Installation
Voltage Drop N/A Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733
Voltage Discharge N/A Discharge to Less than 30 Volts within 30 s After Removal of Power
Operating Temperature N/A -40 to +65 °C
Storage Temperature N/A -55 to +105 °C
Compliance N/A MIL-STD-188-125-1 MIL-STD-188-125-2
Enclosure N/A
  • Modified NEMA 1 type enclosure
  • Cabinets: Stainless steel construction
  • Stand alone filters and inserts: Cold rolled steel construction with a corrosion resistant plating
  • Epoxy paint optional
  • Shielding effectiveness on clean side greater than 100 dB from 14 kHz to 10 GHz
  • Dual removable access covers.
Features N/A
  • Inductive input
  • Individually Filtered Lines
  • Surge arrestors V481BA60 included
  • Custom options available