CAD (0)
▾
Power Line HEMP Filters Standard Performance
HEMP Filters Power, Control, and Signal Lines
- Voltage Rating: 277/480 VAC @ 60 Hz
- Current Rating: 5 through 150 amperes
- HEMP Compliance: Per MIL-STD-188-125-1 and MIL-STD-188-125-2 as Power Line (Intrasite) point of entry filter for short (E1) and intermediate (E2) pulses.
- Insertion Loss: Standard performance (curve 1) per MIL-STD-220
- Leakage Current: < 10% of rated current 10 through 150 amperes, < 1 amp for 5 amp filters
- Insulation Resistance: Per MIL-PRF-15733, prior to discharge resistor installation.
- Dielectric Withstanding Voltage: 2250 VDC line-to-chassis per MIL-STD-202, Method 301 prior to surge arrestor and discharge resistor installation
- Voltage Drop: Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733
- Voltage Discharge: Discharge to less than 30 Volts within 30 s after removal of power
- Operating Temperature: -40 ºC to +65 ºC
- Storage Temperature: -55 ºC to +105 ºC
Unit of Measure
Items |
/ImgCustom/1001/placeholder_notavailable.gif A-10540 5 Ampere (A) Current Power Line Stand Alone HEMP Filter Standard Performance |
/ImgCustom/1001/placeholder_notavailable.gif A-10541 5 Ampere (A) Current Power Line Stand Alone HEMP Filter Standard Performance |
/ImgCustom/1001/placeholder_notavailable.gif A-10542 5 Ampere (A) Current Power Line Stand Alone HEMP Filter Standard Performance |
/ImgCustom/1001/placeholder_notavailable.gif A-10543 10 Ampere (A) Current Power Line Stand Alone HEMP Filter Standard Performance |
/ImgCustom/1001/placeholder_notavailable.gif A-10544 10 Ampere (A) Current Power Line Stand Alone HEMP Filter Standard Performance |
|||||
Description |
N/A
|
|||||||||
Brands | N/A Captor | |||||||||
Voltage Rating (AC) | N/A 277 V480 V | |||||||||
Frequency | N/A 60 Hz | |||||||||
Current | N/A 5 A | N/A 5 A | N/A 5 A | N/A 10 A | N/A 10 A | |||||
Insertion Loss Curve |
N/A
Curve 1, Standard Performance Minimum Insertion Loss |
|||||||||
Number of Circuits | N/A 2 | N/A 3 | N/A 4 | N/A 2 | N/A 3 | |||||
Dimension A | N/A 9.00 in | N/A 13.5 in | N/A 18.00 in | N/A 9.00 in | N/A 13.5 in | |||||
Dimension B | N/A 30.0 in | |||||||||
Dimension C | N/A 5.5 in | |||||||||
Dimension D | N/A 29.0 in | |||||||||
Dimension E | N/A 8.0 in | N/A 12.5 in | N/A 17.0 in | N/A 8.0 in | N/A 12.5 in | |||||
Estimated Weight | N/A 50 lb | N/A 75 lb | N/A 105 lb | N/A 60 lb | N/A 90 lb | |||||
High Altitude Electromagnetic Pulse (HEMP) Compliance | N/A Per MIL-STD-188-125-1 and MIL-STD-188-125-2 as Power Line (Intrasite) Point of Entry Filter for Short (E1) and Intermediate (E2) Pulses. | |||||||||
Minimum Insertion Loss | N/A 20 dB @ 10 kHz 40 dB @ 100 kHz 60 dB @ 1 MHz 80 dB @ 10 MHz to 10 GHz | |||||||||
Leakage Current | N/A < 10% of Rated Current 10 through 150 Amperes, < 1 Amp for 5 Amp Filters | |||||||||
Insulation Resistance | N/A Per MIL-PRF-15733, prior to discharge resistor installation. | |||||||||
Dielectric Withstanding Voltage | N/A 2250 VDC Line-to-Chassis Per MIL-STD-202, Method 301 Prior to Surge Arrestor and Discharge Resistor Installation | |||||||||
Voltage Drop | N/A Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733 | |||||||||
Voltage Discharge | N/A Discharge to Less than 30 Volts within 30 s After Removal of Power | |||||||||
Operating Temperature | N/A -40 to +65 °C | |||||||||
Storage Temperature | N/A -55 to +105 °C | |||||||||
Compliance | N/A MIL-STD-188-125-1 MIL-STD-188-125-2 | |||||||||