CAD (0)
  • Cart is empty
  • Voltage Rating: 277/480 VAC @ 60 Hz
  • Current Rating: 5 through 150 amperes
  • HEMP Compliance: Per MIL-STD-188-125-1 and MIL-STD-188-125-2 as Power Line (Intrasite) point of entry filter for short (E1) and intermediate (E2) pulses.
  • Insertion Loss: high performance (curve 2) per MIL-STD-220
  • Leakage Current: < 10% of rated current 10 through 150 amperes, <1 amp for 5 amp filters
  • Insulation Resistance: Per MIL-PRF-15733, prior to discharge resistor installation.
  • Dielectric Withstanding Voltage: 2250 VDC line-to-chassis per MIL-STD-202, Method 301 prior to surge arrestor and discharge resistor installation
  • Voltage Drop: Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733
  • Voltage Discharge: Discharge to less than 30 Volts within 30 s after removal of power
  • Operating Temperature: -40 ºC to +65 ºC
  • Storage Temperature: -55 ºC to +105 ºC
Unit of Measure
Items
Image

5 Ampere (A) Current Power Line Stand Alone HEMP Filter High Performance

Image

5 Ampere (A) Current Power Line Stand Alone HEMP Filter High Performance

Image

5 Ampere (A) Current Power Line Stand Alone HEMP Filter High Performance

Image

10 Ampere (A) Current Power Line Stand Alone HEMP Filter High Performance

Image

10 Ampere (A) Current Power Line Stand Alone HEMP Filter High Performance
Description N/A
  • Voltage Rating: 277/480 VAC @ 60 Hz
  • Current Rating: 5 through 150 amperes
  • HEMP Compliance: Per MIL-STD-188-125-1 and MIL-STD-188-125-2 as Power Line (Intrasite) point of entry filter for short (E1) and intermediate (E2) pulses.
  • Insertion Loss: high performance (curve 2) per MIL-STD-220
  • Leakage Current: < 10% of rated current 10 through 150 amperes, <1 amp for 5 amp filters
  • Insulation Resistance: Per MIL-PRF-15733, prior to discharge resistor installation.
  • Dielectric Withstanding Voltage: 2250 VDC line-to-chassis per MIL-STD-202, Method 301 prior to surge arrestor and discharge resistor installation
  • Voltage Drop: Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733
  • Voltage Discharge: Discharge to less than 30 Volts within 30 s after removal of power
  • Operating Temperature: -40 ºC to +65 ºC
  • Storage Temperature: -55 ºC to +105 ºC
Brands N/A Captor
Voltage Rating (AC) N/A 277 V480 V
Frequency N/A 60 Hz
Current N/A 5 A N/A 5 A N/A 5 A N/A 10 A N/A 10 A
Insertion Loss Curve N/A
Curve 2, High Performance Minimum Insertion Loss
Number of Circuits N/A 2 N/A 3 N/A 4 N/A 2 N/A 3
Dimension A N/A 9.00 in N/A 13.5 in N/A 18.00 in N/A 9.00 in N/A 13.5 in
Dimension B N/A 36.0 in
Dimension C N/A 5.5 in
Dimension D N/A 35.0 in
Dimension E N/A 8.0 in N/A 12.5 in N/A 17.0 in N/A 8.0 in N/A 12.5 in
Estimated Weight N/A 75 lb N/A 110 lb N/A 145 lb N/A 85 lb N/A 125 lb
High Altitude Electromagnetic Pulse (HEMP) Compliance N/A Per MIL-STD-188-125-1 and MIL-STD-188-125-2 as Power Line (Intrasite) Point of Entry Filter for Short (E1) and Intermediate (E2) Pulses.
Minimum Insertion Loss N/A 100 dB @ 14 kHz to 10 GHz
Leakage Current N/A < 10% of Rated Current 10 through 150 Amperes, < 1 Amp for 5 Amp Filters
Insulation Resistance N/A Per MIL-PRF-15733, prior to discharge resistor installation.
Dielectric Withstanding Voltage N/A 2250 VDC Line-to-Chassis Per MIL-STD-202, Method 301 Prior to Surge Arrestor and Discharge Resistor Installation
Voltage Drop N/A Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733
Voltage Discharge N/A Discharge to Less than 30 Volts within 30 s After Removal of Power
Operating Temperature N/A -40 to +65 °C
Storage Temperature N/A -55 to +105 °C
Compliance N/A MIL-STD-188-125-1 MIL-STD-188-125-2
Enclosure N/A
  • Modified NEMA 1 type enclosure
  • Cabinets: Stainless steel construction
  • Stand alone filters and inserts: Cold rolled steel construction with a corrosion resistant plating
  • Epoxy paint optional
  • Shielding effectiveness on clean side greater than 100 dB from 14 kHz to 10 GHz
  • Dual removable access covers.
Features N/A
  • Inductive input
  • Individually Filtered Lines
  • Surge arrestors V481BA60 included
  • Custom options available
Note N/A Specifications subject to change.